Compliance calendar
for your building.
What has to be inspected, tested and maintained, how often, and whether that is law, a British Standard or guidance. Pick a building type, tick the systems it has, and take the plan away as a calendar file, a printed page or a link.
- 28regimes
- 117tasks
- 37rest on law
- sources checked
Full calendar, all building types
The full calendar.Your building's calendar.
Showing the whole dataset: 28 regimes and 117 tasks, for every building type. 37 rest on law, 30 on a British Standard and 50 on guidance. Choose a building type to cut this down to your building.
- 37LawLegislation says you must do this, at this interval where one is given.
- 30British StandardA British Standard recommends it. Following the standard is the usual way to show the general legal duty has been met, but the interval is not itself law.
- 50GuidanceA regulator, government department or industry body recommends it.
Choose the height of the block in step 01 to see its calendar.
12-month view
Months across, tasks down, a mark where each one falls from the start date
- Law
- British Standard
- Guidance
- A bar means every week
Weekly
8 tasks| Task | How often | Who | Basis |
|---|---|---|---|
| Fire detection and alarm systems Weekly user test from a manual call point, using a different call point each week | Every week | Premises management or nominated staff | British Standard |
| Fire doors (communal and flat entrance doors) Check that fire doors on stairways close effectively on their self-closers | Every week | Responsible person or nominated staff | Guidance |
| Sprinkler systems Weekly tests: alarms, pump or engine start, air compressors, isolating valve positions and frost protection | Every week | Trained and competent member of staff, or the sprinkler contractor | British StandardMedium confidence |
| Smoke control and smoke ventilation (AOVs) Weekly actuation test, rotating zones so that every zone is tested at least once every three months | Every week | Building's competent person | British StandardMedium confidence |
| Voice alarm and public address (PAVA) systems Weekly test with the fire alarm, confirming the correct message is broadcast in the correct zones and is understood | Every week | Premises management or nominated staff | British StandardMedium confidence |
| Firefighting lifts and essential fire-fighting equipment in high-rise residential buildings Weekly operation of the fire-fighting lift override switch | Every week | Responsible person or nominated staff | Guidance |
| Legionella control in hot and cold water systems Flush infrequently used outlets | Every week | Responsible person or nominated staff | Guidance |
| Legionella control in hot and cold water systems Weekly dip slide test of cooling system water | Every week | Water treatment provider or trained staff | Guidance |
Monthly
13 tasks| Task | How often | Who | Basis |
|---|---|---|---|
| Fire detection and alarm systems Monthly routine check of fire detection and alarm systems in the common parts | Every month | Responsible person | Law |
| Emergency lighting Monthly short functional test of every emergency luminaire and exit sign | Every month | Responsible person or nominated staff | British Standard |
| Fire extinguishers Visual check that each extinguisher is in place, undamaged and at the correct pressure | Every month | Responsible person or nominated staff | Guidance |
| Dry and wet rising mains Monthly routine check of rising main inlets and outlets | Every month | Responsible person | Law |
| Sprinkler systems Monthly checks: battery levels and water storage tank security | Every month | Trained and competent member of staff, or the sprinkler contractor | British StandardMedium confidence |
| Sprinkler systems Monthly routine check of the suppression system | Every month | Responsible person | LawMedium confidence |
| Smoke control and smoke ventilation (AOVs) Monthly test of AOVs using the manual controls | Every month | Responsible person or nominated staff | GuidanceMedium confidence |
| Smoke control and smoke ventilation (AOVs) Monthly routine check of smoke control systems | Every month | Responsible person | LawMedium confidence |
| Evacuation alert systems (BS 8629) Monthly routine check of the evacuation alert system, recorded and made available to residents | Every month | Responsible person | LawMedium confidence |
| Firefighting lifts and essential fire-fighting equipment in high-rise residential buildings Monthly routine check of lifts for use by firefighters, evacuation lifts and essential fire-fighting equipment, with a record made available to residents | Every month | Responsible person | Law |
| Legionella control in hot and cold water systems Check cold water temperatures at sentinel taps (below 20 degrees C within two minutes) | Every month | Responsible person or water hygiene contractor | Guidance |
| Legionella control in hot and cold water systems Check hot water temperatures at sentinel points (at least 50 degrees C within one minute, 55 in healthcare) | Every month | Responsible person or water hygiene contractor | Guidance |
| Legionella control in hot and cold water systems Check calorifier flow and return temperatures (flow at 60 degrees C, return not below 50) | Every month | Responsible person or water hygiene contractor | Guidance |
Quarterly
6 tasks| Task | How often | Who | Basis |
|---|---|---|---|
| Fire doors (communal and flat entrance doors) Check all fire doors in communal areas, including that self-closing devices work | Every 3 months | Responsible person | Law |
| Sprinkler systems Quarterly service: review of hazard, pipework and supports, water supply flow tests, stop valves and flow switches | Every 3 months | Sprinkler installer or specialist maintenance contractor | British StandardMedium confidence |
| Kitchen extract (grease) ductwork Clean the entire kitchen extract system, including the canopy, fan and the full length of the ductwork | Every 3 months | Competent kitchen extract cleaning contractor | Guidance |
| F-gas leak checks on air conditioning, refrigeration and heat pumps Leak check by a certified technician | Every 3 monthsEvery 3 months, or every 6 months with the leak detection system that article 5 requires | Operator of the equipment, using an F-gas certified technician | Law |
| Legionella control in hot and cold water systems Dismantle, clean and descale shower heads, hoses and spray taps | Every 3 months | Responsible person or water hygiene contractor | Guidance |
| Legionella control in hot and cold water systems Legionella sampling of cooling system water | Every 3 months | Water treatment provider | Guidance |
Six-monthly
14 tasks| Task | How often | Who | Basis |
|---|---|---|---|
| Fire detection and alarm systems Inspection and servicing by a competent fire alarm contractor | Every 6 monthsApproximately every 6 months: each visit may fall between 5 and 7 months after the last | Competent fire alarm contractor | British Standard |
| Emergency lighting More detailed condition test including a three hour battery test | Every 6 months | Competent person | Guidance |
| Fire doors (communal and flat entrance doors) Inspect fire doors for damage, fit in the frame and effective self-closing | Every 6 months | Responsible person or competent fire door inspector | Guidance |
| Dry and wet rising mains Inspection of the fire main, including outlets, landing valves, padlocks and straps | Every 6 months | Responsible person or riser contractor | British Standard |
| Sprinkler systems Six-monthly tasks: alternate system changeover and check of the electrical signal to the fire brigade | Every 6 months | Sprinkler installer or specialist maintenance contractor | British StandardMedium confidence |
| Smoke control and smoke ventilation (AOVs) Six-monthly inspection and maintenance by a competent maintainer | Every 6 months | Competent smoke control maintainer | GuidanceMedium confidence |
| Gaseous fire suppression systems (including room integrity testing) Service visit by a suppression specialist, including a check that pressure relief vents are free to operate | Every 6 months | Competent gaseous suppression contractor | GuidanceMedium confidence |
| Voice alarm and public address (PAVA) systems Six-monthly maintenance inspection by a competent organisation | Every 6 months | Competent voice alarm maintenance organisation | British StandardMedium confidence |
| Kitchen extract (grease) ductwork Clean the entire kitchen extract system, including the canopy, fan and the full length of the ductwork | Every 6 months | Competent kitchen extract cleaning contractor | Guidance |
| Lightning protection systems Visual inspection between annual tests | Every 6 months | Competent lightning protection specialist | GuidanceMedium confidence |
| Passenger and goods lifts (thorough examination) Thorough examination by a competent person | Every 6 months | Competent person, sufficiently independent of the lift's routine maintenance | Law |
| F-gas leak checks on air conditioning, refrigeration and heat pumps Leak check by a certified technician | Every 6 months | Operator of the equipment, using an F-gas certified technician | Law |
| Fall-arrest anchors and personal fall protection equipment Periodic examination of anchors used for rope access or for raising and lowering people | Every 6 months | Competent anchor examiner | British StandardMedium confidence |
| Fall-arrest anchors and personal fall protection equipment Detailed inspection of harnesses, lanyards and other webbing or rope equipment | Every 6 months | Competent person appointed by the employer | GuidanceMedium confidence |
Annual
35 tasks| Task | How often | Who | Basis |
|---|---|---|---|
| Emergency lighting Annual full rated duration test (usually three hours) | Every year | Competent contractor | British Standard |
| Fire doors (communal and flat entrance doors) Check flat entrance doors, including self-closing devices (best endeavours) | Every year | Responsible person | Law |
| Fire extinguishers Basic service by a competent extinguisher technician | Every year | Competent extinguisher technician | British Standard |
| Dry and wet rising mains Annual test of the rising main (a pressure test for dry risers) | Every year | Specialist riser contractor | British Standard |
| Sprinkler systems Annual service: pumps, engine, tank float valves and valve inspection | Every year | Sprinkler installer or specialist maintenance contractor | British StandardMedium confidence |
| Sprinkler systems Annual inspection by the installer | Every year | Sprinkler installer | British StandardMedium confidence |
| Smoke control and smoke ventilation (AOVs) Annual maintenance check, including detectors, controls and performance against the design | Every year | Certified smoke control contractor | GuidanceMedium confidence |
| Fire and smoke dampers Test every fire and smoke damper (drop test or actuation), clean and lubricate, and record with photographs | Every year | Competent fire damper specialist | British StandardMedium confidence |
| Fire and smoke dampers Test all fire and smoke dampers as part of the annual verification of ventilation systems | Every year | Competent person under the healthcare ventilation regime | GuidanceMedium confidence |
| Gaseous fire suppression systems (including room integrity testing) Room integrity test and hold time calculation | Every year | Competent room integrity tester | British StandardMedium confidence |
| Voice alarm and public address (PAVA) systems Twelve-monthly maintenance inspection, including the annual checks | Every year | Competent voice alarm maintenance organisation | British StandardMedium confidence |
| Firefighting lifts and essential fire-fighting equipment in high-rise residential buildings Inspect the secure information box and confirm it is still accessible to the fire and rescue service, secure and able to hold the required documents | Every yearAt least once a year | Responsible person | Law |
| Firefighting lifts and essential fire-fighting equipment in high-rise residential buildings Annual testing and maintenance of fire-fighting lifts | Every year | Competent lift contractor | Guidance |
| Kitchen extract (grease) ductwork Clean the entire kitchen extract system, including the canopy, fan and the full length of the ductwork | Every year | Competent kitchen extract cleaning contractor | Guidance |
| Fire risk assessment review Review the fire risk assessment | Every year | Responsible person or competent fire risk assessor | Guidance |
| Fire risk assessment review Review the fire risk assessment | Every yearRange given by the source: every 1 to 3 years | Responsible body or competent fire risk assessor | Guidance |
| Fire risk assessment review Review each person-centred fire risk assessment and emergency evacuation statement | Every yearAt least every 12 months, and sooner on request or if circumstances change | Responsible person | Law |
| Fire risk assessment review Review the building emergency evacuation plan | Every yearAt least every 12 months, and sooner if the plan needs amending | Responsible person | Law |
| Fixed wiring inspection (EICR) Periodic inspection and test | Every year | Competent electrical inspector | Guidance |
| Lightning protection systems Visual inspection and electrical test of the whole system by a lightning protection specialist | Every year | Competent lightning protection specialist | British StandardMedium confidence |
| Gas appliance safety checks Gas safety check of every appliance and flue provided by the landlord, with a record | Every year | Landlord, using a Gas Safe registered engineer | Law |
| Gas appliance safety checks Service gas appliances and flues | Every year | Gas Safe registered engineer | Guidance |
| Gas appliance safety checks Planned maintenance and safety checks of gas appliances, pipework and flues | Every yearNo legal interval; at least annually is accepted good practice | Employer or person in control, using a Gas Safe registered engineer | Guidance |
| Passenger and goods lifts (thorough examination) Thorough examination by a competent person | Every year | Competent person | Law |
| F-gas leak checks on air conditioning, refrigeration and heat pumps Leak check by a certified technician | Every year | Operator of the equipment, using an F-gas certified technician | Law |
| F-gas leak checks on air conditioning, refrigeration and heat pumps Check the automatic leak detection system | Every year | F-gas certified technician | Law |
| Ventilation hygiene (ductwork inspection and cleaning) Inspect the ventilation system for cleanliness (visual assessment, deposit measurement and photographs) | Every year | Competent ventilation hygiene specialist | GuidanceMedium confidence |
| Ventilation hygiene (ductwork inspection and cleaning) Visual inspection of every ventilation system | Every year | Competent person under the healthcare ventilation regime | GuidanceMedium confidence |
| Local exhaust ventilation (LEV) Thorough examination and test of each LEV system by a competent person | Every 14 monthsMaximum of 14 months; Schedule 4 of COSHH sets shorter intervals for certain processes | Employer, using a competent LEV examiner | Law |
| Legionella control in hot and cold water systems Inspect cold water storage tanks and carry out remedial work | Every year | Water hygiene contractor | Guidance |
| Legionella control in hot and cold water systems Inspect and clean calorifiers internally | Every year | Water hygiene contractor | Guidance |
| Legionella control in hot and cold water systems Maintain thermostatic mixing valves, including cleaning strainers and filters | Every year | Competent person | Guidance |
| Asbestos management (re-inspection) Review the asbestos management plan, register and drawings | Every year | Dutyholder | Guidance |
| Asbestos management (re-inspection) Re-inspect known or presumed asbestos-containing materials and record their condition | Every yearAt least every 12 months in most cases; more often for materials in busy or vulnerable locations | Dutyholder, using a competent person | Guidance |
| Fall-arrest anchors and personal fall protection equipment Periodic examination of fall-arrest anchor devices by a competent person | Every year | Competent anchor examiner | British StandardMedium confidence |
Every few years
17 tasks| Task | How often | Who | Basis |
|---|---|---|---|
| Emergency lighting Photometric verification of light levels | Every 5 years | Competent emergency lighting specialist | British Standard |
| Fire extinguishers Extended service, including discharge, internal inspection and refill | Every 5 years | Competent extinguisher technician | British Standard |
| Fire extinguishers Overhaul, including hydraulic pressure test of the cylinder and a new valve | Every 10 years | Competent extinguisher technician | British Standard |
| Sprinkler systems Three-yearly inspection of tanks, valves and non-return valves | Every 3 years | Sprinkler installer or specialist maintenance contractor | British StandardMedium confidence |
| Sprinkler systems Drain, clean and internally examine water storage tanks | Every 10 years | Competent person | British StandardMedium confidence |
| Fire risk assessment review Review the fire risk assessment | Every 2 years | Responsible person or competent fire risk assessor | Guidance |
| Fire risk assessment review Carry out a new fire risk assessment | Every 4 years | Competent fire risk assessor | Guidance |
| Fire risk assessment review Carry out a new fire risk assessment | Every 3 years | Competent fire risk assessor | Guidance |
| Building registration and safety case for higher-risk residential buildings Expect reassessment of the building assessment certificate | Every 5 yearsRegulator's stated aim, not a legal interval; process under review since July 2026 | Building Safety Regulator, with the principal accountable person | GuidanceMedium confidence |
| Building registration and safety case for higher-risk residential buildings Review the residents' engagement strategy | Every 2 yearsAt least every 2 years, and after certain events | Principal accountable person | LawMedium confidence |
| Fixed wiring inspection (EICR) Inspect and test the electrical installation and obtain a report (EICR) | Every 5 yearsMaximum of 5 years, or earlier if the previous report sets an earlier date | Landlord, using a qualified and competent inspector | Law |
| Fixed wiring inspection (EICR) Periodic inspection and test (EICR) | Every 5 yearsTypical period; the inspector may recommend a shorter interval | Competent electrical inspector | Guidance |
| Fixed wiring inspection (EICR) Periodic inspection and test (EICR) | Every 3 yearsTypical period; the inspector may recommend a shorter interval | Competent electrical inspector | Guidance |
| Fixed wiring inspection (EICR) Inspection and test of the electrical installation | Every 5 years | Competent electrical contractor | Guidance |
| Portable appliance testing (PAT) Check (visual inspection, testing or both) each item of electrical equipment the landlord provides | Every 5 yearsMaximum of 5 years, or earlier if the previous record sets an earlier date | Registered provider of social housing, using a qualified person | Law |
| Air conditioning energy inspections (TM44) Air conditioning inspection by an accredited energy assessor, with a report | Every 5 years | Person who controls the operation of the system, using an accredited energy assessor | Law |
| Ventilation hygiene (ductwork inspection and cleaning) Risk assessment survey of ductwork cleanliness to BS EN 15780 | Every 2 yearsAt least every 2 years in most facilities; annually in higher-risk environments. Range given by the source: every 1 to 2 years | Competent ventilation hygiene specialist | British StandardMedium confidence |
No fixed interval
24 tasksThese tasks are not on a fixed cycle. The interval is set by a risk assessment, by an event or by a written scheme, as each row explains. They are left out of the calendar file, so put them in your diary by hand.
| Task | How often | Who | Basis |
|---|---|---|---|
| Fire and smoke dampers More frequent testing of dampers in dust-laden or polluted airstreams | No fixed intervalMore often than annually, at a period suited to the degree of pollution | Competent fire damper specialist | British StandardMedium confidence |
| Gaseous fire suppression systems (including room integrity testing) F-gas leak checks on systems that contain fluorinated extinguishing agents | No fixed intervalEvery 12, 6 or 3 months depending on the charge: see the F-gas leak checks entry | F-gas certified technician | LawMedium confidence |
| Evacuation alert systems (BS 8629) Report any fault that cannot be fixed within 24 hours to the local fire and rescue service, and report again when it is fixed | No fixed intervalEvent-driven: as soon as reasonably practicable, where a fault cannot be fixed within 24 hours of being found | Responsible person | LawMedium confidence |
| Evacuation alert systems (BS 8629) Inspection and servicing by a competent contractor | No fixed intervalFollow BS 8629 and the manufacturer's instructions; interval not verified | Competent evacuation alert system contractor | British StandardMedium confidence |
| Firefighting lifts and essential fire-fighting equipment in high-rise residential buildings Report any fault that cannot be fixed within 24 hours to the local fire and rescue service, and report again when it is fixed | No fixed intervalEvent-driven: as soon as reasonably practicable, where a fault cannot be fixed within 24 hours of being found | Responsible person | Law |
| Fire risk assessment review Review the fire risk assessment regularly, and whenever it may no longer be valid or there has been a significant change | No fixed intervalNo fixed legal interval: regularly, and on any significant change to the premises, their use or the fire precautions | Responsible person | Law |
| Building registration and safety case for higher-risk residential buildings Register the building with the Building Safety Regulator before it is occupied | No fixed intervalOne-off, before occupation | Principal accountable person | LawMedium confidence |
| Building registration and safety case for higher-risk residential buildings Give the regulator the structure and fire safety information (key building information) | No fixed intervalWithin 28 days of applying to register | Principal accountable person | LawMedium confidence |
| Building registration and safety case for higher-risk residential buildings Tell the regulator about changes to the registration details | No fixed intervalEvent-driven: within 14 relevant days (Christmas Day, Good Friday and bank holidays do not count) or 28 days of becoming aware of the change | Principal accountable person | LawMedium confidence |
| Building registration and safety case for higher-risk residential buildings Assess building safety risks (spread of fire and structural failure), and reassess | No fixed intervalNo fixed legal interval: at regular intervals and when the assessment may no longer be valid | Each accountable person | LawMedium confidence |
| Building registration and safety case for higher-risk residential buildings Keep the safety case report up to date and tell the regulator about significant updates | No fixed intervalNo fixed interval: revise after each further risk assessment or new safety measure | Principal accountable person | LawMedium confidence |
| Building registration and safety case for higher-risk residential buildings Apply for a building assessment certificate when directed by the regulator | No fixed intervalWithin 28 days of the direction | Principal accountable person | LawMedium confidence |
| Building registration and safety case for higher-risk residential buildings Report safety occurrences to the regulator | No fixed intervalEvent-driven: notice as soon as reasonably practicable, report within 10 days | Principal accountable person or accountable person | LawMedium confidence |
| Portable appliance testing (PAT) Formal visual inspection | Every 6 months to 1 yearA range, not a single fixed interval | Trained member of staff or competent person | Guidance |
| Portable appliance testing (PAT) Combined inspection and test (PAT) | Every 1 to 2 yearsA range, not a single fixed interval | Competent person with suitable test equipment | Guidance |
| Portable appliance testing (PAT) Formal visual inspection (no test needed) | Every 6 months to 1 yearA range, not a single fixed interval | Trained member of staff or competent person | Guidance |
| Portable appliance testing (PAT) Formal visual inspection (no test needed if double insulated; otherwise test up to every 5 years) | Every 2 to 4 yearsA range, not a single fixed interval | Trained member of staff or competent person | Guidance |
| Portable appliance testing (PAT) Formal visual inspection and, where the equipment is earthed, combined inspection and test | Every 6 months to 5 yearsA range, not a single fixed interval | Trained member of staff or competent person | Guidance |
| Pressure systems (written scheme of examination) Have a written scheme of examination drawn up or certified by a competent person | No fixed intervalOne-off, before first use; keep the scheme under review | User of the installed system (or owner of a mobile system) | Law |
| Pressure systems (written scheme of examination) Examination of the system by a competent person in accordance with the written scheme | No fixed intervalInterval is set by the written scheme for each part of the system | Competent person (often an engineering inspection body) | Law |
| Passenger and goods lifts (thorough examination) Thorough examination after exceptional circumstances, such as damage, failure or a long period out of use | No fixed intervalEvent-driven | Competent person | Law |
| Ventilation hygiene (ductwork inspection and cleaning) Clean ductwork and air handling plant when inspection shows deposits above the limit | No fixed intervalCondition-based: when inspection results require it | Competent ventilation hygiene contractor | GuidanceMedium confidence |
| Local exhaust ventilation (LEV) Routine user checks of the LEV system (airflow indicators, hoods, ducts and filters) | No fixed intervalDaily, weekly and monthly checks as set out in the system's user manual and logbook | Operators and supervisors | Guidance |
| Legionella control in hot and cold water systems Review the legionella risk assessment | No fixed intervalNo fixed interval: regularly, and after changes to the water system, its use or the building | Dutyholder and appointed responsible person | Guidance |